IMPORTANT
These air conditioners employ new
refrigerant R410A.
Pay special attention when
servicing the unit.
TECHNICAL & SERVICE MANUAL
KHS3082 + CH3082
KHS3682 + CH3682
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
Destination: North America
Outdoor Model No.
CH3082
CH3682
Product Code No.
1 852 354 32
1 852 354 33
Indoor Unit Outdoor Unit
KHS3082
KHS3682
CH3082
CH3682
Indoor Model No.
KHS3082
KHS3682
Product Code No.
1 852 354 28
1 852 354 29
REFERENCE NO.
SM700858
FILE NO.
Vista de pagina 0
1 2 3 4 5 6 ... 108 109

Indice de contenidos

Pagina 1 - KHS3682 + CH3682

IMPORTANTThese air conditioners employ newrefrigerant R410A.Pay special attention whenservicing the unit.TECHNICAL & SERVICE MANUALKHS3082 + CH308

Pagina 2 - SAFETY PRECAUTIONS

Indoor Unit KHS3682Outdoor Unit CH3682< 208V > DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperat

Pagina 3 - Prohibit

224. How to Install the Outdoor UnitFirst refer to Section 2. Installation Site Selection.4-1. Wiring Instructions for the Outdoor UnitRegulations on

Pagina 4 - Table of Contents

235. Refrigerant Tubing5-1. Use of the Flaring MethodMany of the conventional split system air conditionersemploy the flaring method to connect refrig

Pagina 5

245-4. Connecting Tubing between Indoor and Outdoor Unitsa) Tightly connect the indoor side refrigerant tubing exten-ded from the wall with the outdoo

Pagina 6 - 1. OPERATING RANGE

256. Air PurgingAir and moisture remaining in the refrigerant systemhave undesirable effects as indicated below. Therefore,they must be purged complet

Pagina 7 - 2. SPECIFICATIONS

26(5) With the vacuum pump still running, close the “Lo”knob of the manifold valve. Then stop the vacuumpump.(6) With the hex wrench, turn the valve s

Pagina 8 - Outdoor Unit CH3082

27How to Test Run the Air ConditionerAfter turning on the power of the air conditioner, use theremote controller and follow the steps below to conduct

Pagina 9 - < 230V >

28 Pump DownPump down means collecting all refrigerant gas in thesystem back into the outdoor unit without losing any ofthe gas. Pump down is used wh

Pagina 10 - < 208V >

a) Temporary connection:Screw in 3 – 5 turns by hand. (Fig. 60c)b) To fasten the flare nuts, apply specified torqueas Table 9 and Fig. 60d.Fig. 60c Fi

Pagina 11 - 2-2-1. Indoor Unit

308. Address Switch8-1. Address Setting of the Remote Control UnitThe address can be set in order to prevent interferencebetween remote controllers wh

Pagina 12

For Parts or Service Assistance please contact your local Sanyo HVAC Contractor or DistributorUnited States: SCS, HVAC SolutionsWeb: www.SanyoHVAC.com

Pagina 13 - 2-2-2. Outdoor Unit

Indoor Unit KHS308224BYJ48-1256Flap MotorType Stepping MotorRating ModelCoil Resistance Ohm(Ambient Temp. 77 °F (25 °C))Each Pair of Terminal : 200 +/

Pagina 14

Indoor Unit KHS3682Flap MotorTypeRating ModelCoil Resistance Ohm(Ambient Temp. 77 °F (25 °C)) Face Area CoilRowsFins Per inchHeat Exchanger Coilft2 (m

Pagina 15

Outdoor Unit CH30822-2-2. Outdoor UnitP.C.BoardCircuit Fuse ControlsPart No.-250V 25APOW-CH3082-B1Noise Filer P.C.BMicroprocessor400V 3.5ACR-CH3082-F

Pagina 16 - 3. DIMENSIONAL DATA

Outdoor Unit CH3682P.C.BoardCircuit Fuse ControlsPart No.-250V 25APOW-CH3082-B1Noise Filer P.C.BMicroprocessor400V 3.5ACR-CH3682-FControl P.C.B--HIC-C

Pagina 17 -  CH3682

2-3. Other Component Specifications Indoor Unit KHS3082 KHS3682Outdoor Unit CH3082 CH3682032 50 68 86 104 122 140 158 176 194(0) (10) (20) (30) (

Pagina 18 - 4. REFRIGERANT FLOW DIAGRAM

3. DIMENSIONAL DATAIndoor Unit  KHS3082 KHS3682Unit: inch(mm)(852-0-0010-19600-0)41-15/16 (1065)9-1/16 (230) (3/32)7-25/32Wide tube dia. 5/8"

Pagina 19 - 5. PERFORMANCE DATA

Outdoor Unit CH3082 CH3682Unit: inch(mm)(852-0-0010-19400-1)6-11/6 25-31/32 4-11/322-15/162-3/82-ID:1-1/4 holes (holes for drain)Of the 4-ID:1-1/4

Pagina 20 - Indoor air temp.73

Compressor4-wayvalveMainAccumulatorHigh pressureswitchWide tubeservicevalveWide tubeSubAccumulatorNarrowtubeservicevalveNarrow tubeHeat exchangerHeat

Pagina 21 - Hi FanLo fan

5. PERFORMANCE DATA5-1. Temperature ChartsIndoor Unit KHS3082Outdoor Unit CH3082• Check each performance value in test-run mode. Electrical perfor

Pagina 22

• Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them. • The precautionary items here

Pagina 23 - 5-2. Cooling Capacity

Indoor Unit KHS3082Outdoor Unit CH3082• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/o

Pagina 24 - < Cooling Capacity >

Indoor Unit KHS3682Outdoor Unit CH3682Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)(1) Low pressure performance cha

Pagina 25 - Outdoor Unit : CH3682

Indoor Unit KHS3682Outdoor Unit CH3682Indoor discharge air temperature °F(°C)23(–5)32(0)41(5)50(10)59(15)68(20)77(25)Outdoor inlet air D.B. temp.

Pagina 26

Indoor Unit : KHS3082Outdoor Unit : CH3082Power Supply : 230V Single Phase 60Hz< Cooling Capacity (Low Ambient) >5-2. Cooling CapacityTC

Pagina 27 - 5-3. Heating Capacity

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.: Outdoor Ambient Temp. 95 °F (35 °C) D.B.2.3. A

Pagina 28

Indoor Unit : KHS3682Outdoor Unit : CH3682Power Supply : 230V Single Phase 60Hz< Cooling Capacity (Low Ambient) >TC : Total Cooling Capaci

Pagina 29 - Indoor Unit KHS3082

Indoor Unit : KHS3682Outdoor Unit : CH3682Power Supply : 230V Single Phase 60Hz< Cooling Capacity >TC : Total Cooling Capacity (BTU/h) S

Pagina 30 - Indoor Unit KHS3682

Indoor Unit : KHS3082Outdoor Unit : CH3082Power Supply : 230V Single Phase 60Hz< Heating Capacity >5-3. Heating CapacityTH : Total Heatin

Pagina 31 - 6. ELECTRICAL DATA

Indoor Unit : KHS3682Outdoor Unit : CH3682Power Supply : 230V Single Phase 60Hz< Heating Capacity >TH : Total Heating Capacity (BTU/h)1.Ra

Pagina 32 - Outdoor Unit

Horizontal distance (ft.)Axis air velocity (ft./sec.)Vertical distance (ft.)Room air temp. :70°F (21.1°C)Fan speed : HighHeatingHorizontal distance (f

Pagina 33 -  KHS3682

WarningIf refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.If refrigerant gas leaks during the wo

Pagina 34

Horizontal distance (ft.)Axis air velocity (ft./sec.)Vertical distance (ft.)Room air temp. :70°F (21.1°C)Fan speed : HighHeatingHorizontal distance (f

Pagina 35 - 7. FUNCTIONS

6. ELECTRICAL DATA6-1. Electrical CharacteristicsIndoor UnitKHS3082Outdoor UnitCH3082Indoor Unit Outdoor UnitFan Motor Fan Motor + CompressorPerfo

Pagina 36 - Timer backup

Indoor UnitKHS3682Outdoor UnitCH3682Indoor Unit Outdoor UnitFan Motor Fan Motor + CompressorPerformance at 230V Single-phase 60HzRating conditions

Pagina 37 - Slide downward

8FA2-5250-70400-36-2. Electric Wiring DiagramsIndoor Unit KHS3082 KHS3682EVAPORATORTERMINAL BASETO OUTDOOR UNITLAMP9P(WHT)FLAP5P (WHT)MFLAP MOTORRE

Pagina 38

Outdoor Unit CH3082 CH36828FA2-5250-70000-112345INDOORUNITPOWER SUPPLYGNDTERMINAL (5P)CRANKCASEHEATERFAN MOTOR MAGNETIC COILCOIL THERMISTORNOISE

Pagina 39 - 7-2. Protective Functions

Emergency operation SENSOR DRYAUTO cooling/heating operation Selecting the operation mode During DRY operation, the system adjusts the room temperat

Pagina 40 - Defrost detection and release

HIGH POWERNIGHT SETBACKLamp colorsTimer backupThis function acts to raise the power but keeps the AC system in the same operating mode.This function i

Pagina 41 - 8. TROUBLESHOOTING

The noise reducing control is the function used for silent operation of the air conditioner by means of setting the dip switch on the outdoor unit P.C

Pagina 42 - INDOOR UNIT

The maximum current value is changed to 14A (for CH3082) or 17A (for CH3682) to prevent power breaker tripping. (It is set to 24A (in cooling) or 22A

Pagina 43

Overload prevention during heatingDuring HEAT operation, the temperature of the indoor heat exchanger is used to control the frequency and lessen the

Pagina 44 - (2) Checking the outdoor unit

Table of Contents SAFETY PRECAUTIONSTABLE OF CONTENTS1. OPERATING RANGE2. SPECIFICATIONS2-1. Unit Specifications 2-2. Major Component Specifi

Pagina 45 - (3) (2) (1)

This function prevents the circuit breaker or fuse from operating to open the circuit. This function works when electrical current has increased due t

Pagina 46 - Defect or connection error

8. TROUBLESHOOTING8-1. Precautions before Performing Inspection or RepairNOTEAfter checking the self-diagnostics monitor, turn the power OFF before

Pagina 47

Since the indications cover various units, the corresponding parts listed below may not be present in some models.(1) OPERATION lamp(2) TIMER lamp(

Pagina 48 - 8-4-1. Indoor Fan Motor

(2) If the self-diagnostics function fails to operateCheck the indoor unit.Is the fuse blown?Replace the controller.Replace the circuitboard or the fu

Pagina 49 - 8-4-2. Outdoor Fan Motor

8-3. Checking the Indoor and Outdoor Units(1) Checking the indoor unit(2) Checking the outdoor unit Using the TEST/T-RUN terminalsControlNo. Check ite

Pagina 50 - (1) Noise malfunction

(3) Serial Communication Error Identification ProcedureRefer to "Method of Self-Diagnostics" for the self-diagnostics procedure.(3-1) Alarm

Pagina 51 - Resistance

What is the latest self-diagnosis result ?Alarm Code : E07/P04/P05/P20/P27Alarm Code : E07/P04/P05/P20/P27Defect in the outdoor unitP. C. board.Alarm

Pagina 52 - PCB Ass'y

(3-2) Alarm Code : E07/P04/P05/P20/P27Troubleshooting Serial Communication1. Turn off the power and wait until the power lamp (LED) of the outdoor u

Pagina 53 - 10. REFRIGERANT R410A:

[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the indoor unit operates.(There is trouble in the sys

Pagina 54

8-4-2. Outdoor Fan MotorThis outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and

Pagina 55

9. CHECKING ELECTRICAL COMPONENTS9-1. Measurement of Insulation Resistance9-2. Checking Continuity of Fuse on PCB Ass'y10. REFRIGERANT R410A:

Pagina 56

8-5. Noise Malfunction and Electromagnetic InterferenceAn inverter A/C operates using pulse signal control and high frequencies. Therefore, it is sus

Pagina 57

Insulation testerProbeClipGround wireTerminal plateCoppertube ormetallic partClipInsulation testerProbeFig. 1Fig. 2Fig. 3Fig. 4Coppertube ormetallic p

Pagina 58

FusePCB Ass'yFig. 5Fig. 6Fuse9-2. Checking Continuity of Fuse on PCB Ass'yRemove the PCB Ass'y from the electrical component box. Then

Pagina 59

10. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT10-1. Characteristics of New Refrigerant R410A10-1-1. What is New Refrigerant R410A?R

Pagina 60 - APPENDIX A

Tubing precautionsRefrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the t

Pagina 61 - This air conditioner uses

10-3. Tools Specifically for R410A For servicing, use the following tools for R410AGauge manifoldCharging hoseGas leak detectorRefrigerant cylinderCh

Pagina 62 - CONTENTS

10-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly a

Pagina 63 - OI-149-3-EG

ValveSingle valveCharge liquid refrigerant with cylinder in up-side-down position.Single valve (with siphon tube)Charge with cylinder in normal positi

Pagina 64 - UNIT DISPLAY AND OPERATION

Length of tubingEvacuation timeLess than 33 ft. (10 m)More than 10 minutesMore than 33 ft. (10 m)More than 15 minutes10-6. In Case Refrigerant is Le

Pagina 65 - REMOTE CONTROL UNIT (DISPLAY)

10-7. Charging Additional Refrigerant10-7-1. When Tubes are ExtendedObserve the proper amount of refrigerant as stated in this service manual or the

Pagina 66 - REMOTE CONTROL UNIT

95 °F D.B. / 71 °F W.B.67 °F D.B. / 57 °F W.B.80 °F D.B. / 67 °F W.B. _ D.B. / _ W.B.1. OPERATING RANGEMaximumMinimumMaximumMinimum115 °F D.B.0 °

Pagina 67 - OI-149-7-EG

INSTRUCTION MANUALKHS3082 + CH3082KHS3682 + CH3682(OI-852-6-4181-149-00-0)APPENDIX AA-1

Pagina 68 - USING THE REMOTE CONTROL UNIT

KHS3082KHS3682COOL/DRY/HEAT Model© SANYO 2010Pub. OI-85264181149000INSTRUCTION MANUALInverter-Controlled Split System Air ConditionerMODE D’EMPLOIClim

Pagina 69 - 2. Manual Operation

2FEATURESThis air conditioner is an inverter type unit that automatically adjusts capability as appropriate. Details on these functions are provided b

Pagina 70 - 6. QUIET Mode

3PRODUCT INFORMATIONIf you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbe

Pagina 71 - 9. UNOCCUPIED Mode

4NAMES OF PARTSThis illustration is based on the external view of a standard model.Consequently, the shape may differ from that of the air conditioner

Pagina 72 - SPECIAL REMARKS

5REMOTE CONTROL UNIT (DISPLAY)(1) Operation modeAUTO ...HEAT...MILD DRY ...

Pagina 73 - SETTING THE TIMER

6REMOTE CONTROL UNITTransmitterWhen you press the buttons on the remote control unit, the mark appears in the display to transmit the setting change

Pagina 74 - TIPS FOR ENERGY SAVING

7SensorA temperature sensor inside the remote control unit senses the room temperature.(Cover closed)CLOCK buttonACL button (ALL CLEAR)Puts the remote

Pagina 75 - CARE AND CLEANING

8USING THE REMOTE CONTROL UNITHOW TO INSTALL BATTERIES1. Slide the cover in the direction indicated by the arrow and remove it.2. Install two AAA alka

Pagina 76 - OI-149-16-EG

9OPERATION WITH THE REMOTE CONTROL UNIT1. Automatic OperationThis unit automatically switches between cooling operation and heating operation accordin

Pagina 77 - WIRED REMOTE CONTROLLER

2. SPECIFICATIONS2-1. Unit SpecificationsIndoor Unit KHS3082Outdoor Unit CH3082< 230V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating c

Pagina 78

103. Adjusting the Fan SpeedA. Automatic fan speedSimply set the FAN SPEED selector button to the position.This automatically sets the best fan spe

Pagina 79 - INSTALLATION INSTRUCTIONS

117. HIGH POWER ModeHIGH POWER mode can be used to increase the output of the indoor unit for all operation modes except automatic operation.Press th

Pagina 80 - SPECIAL PRECAUTIONS

12A. In Heating Mode: ( )B. In Cooling Mode: ( )• Unoccupied Mode triggers Heating or Cooling Operation in response to the room temperature, but when

Pagina 81 - 1. General

13SETTING THE TIMERIn the descriptions below, the following settings are used for the temperature and time indicator selector button on the bottom fro

Pagina 82

144. How to set daily ON/OFF repeat timer(Example) To start operation at 7:10 am. and stop the air conditioner at 11:00 am. • The ON/OFF combination t

Pagina 83 - Min. 8" (20 cm)

15ADJUSTING THE AIRFLOW DIRECTION1. HorizontalThe horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right

Pagina 84 - About 1/2 of the unit height

16If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning the grille, be careful not to force the vanes ou

Pagina 85 - Unit: inch

17RemountingGrasp the sections near the front panel arms on both sides, and hold the front panel so that it is nearly horizontal. Push the arm shafts

Pagina 86

INSTALLATION INSTRUCTIONSAPPENDIX BKHS3082 + CH3082KHS3682 + CH3682(II-852-6-4190-498-00-0)A-2

Pagina 87

ContentsPageIMPORTANT!Please Read Before Starting ... 21. GENERAL ...

Pagina 88

Indoor Unit KHS3082Outdoor Unit CH3082< 208V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperatu

Pagina 89

2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and operatingstandards. As the installer or service person, it

Pagina 90

31. GeneralThis booklet briefly outlines where and how to install theair conditioning system. Please read over the entire setof instructions for the i

Pagina 91 - Rawl plug

41-5. Additional Materials Required for Installation1. Refrigeration (armored) tape2. Insulated staples or clamps for connecting wire(See local codes.

Pagina 92

● Concerning air-intake side distance “A” (Fig. 5a)The minimum for distance “A” is 6" if there are noobstructions on the air-discharge side (wall

Pagina 93

6Fig. 5eFig. 5fFig. 5g2-2-1. Installing the Unit in an Area with High Winds and in a Snowy Area● In locations with high winds, a wind-proof duct sho

Pagina 94 - OUTDOOR

711-13/16" 13-3/8"25-3/16"22-7/8"(6-21/32")6-5/16"21-25/32" (12-9/16")2-11/16"35-13/16"37-1/32"

Pagina 95

8Required space around the outdoor unitIf the wind-proof duct is used, the space shown below must be secured around the outdoor unit.If the unit is us

Pagina 96 - Strip 3/8" (10 mm)

925-13/32"3/32"13-3/8"(11-15/16")16-15/16"Air IntakeAir discharge39-1/4"27-7/32"7-1/32"35-15/16"28-15/16&

Pagina 97 - Rear panel

10Reference diagram for snow-proof ductSpace requirements for settingCH3082/3682 with STK-BDV80EMin. 39-3/8" or more(1) Single-unit installation(

Pagina 98 - Drain cap

11Min. 39-3/8"or moreMin. 11-13/16"or moreMin. 11-13/16"or moreMin. 19-11/16"or moreMin. 59-1/16"or moreMin. 78-3/4"or m

Pagina 99

Indoor Unit KHS3682Outdoor Unit CH3682< 230V >DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperatu

Pagina 100 - (conduit)

Rear panelFig. 7cRear panelFig. 7b12Set screw only for transportationFig. 6Rear panelmarksFig. 7aLefttubingRighttubingRight-reartubing(recommended)Rig

Pagina 101 - 5. Refrigerant Tubing

13IndoorsideOutdoorsideHole should be made at a slight downward slant to theoutdoor side.NOTEFig. 10Plastic coverINSIDE OUTSIDEWallSlightanglePVC pipe

Pagina 102 - Apply putty here

3-4. Removing and Installing the GrilleBasically, these models can be installed and wired with-out removing the grille. If access to any internal part

Pagina 103 - 6. Air Purging

153-5. Shape the Indoor Side Tubing(1) Arrangement of tubing by directiona) Right or left tubingCut out the corner of the right/left frame with ahacks

Pagina 104

163-7. Wire Size and LengthRegulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local

Pagina 105

173-8. Wiring Instructions for Inter-unit Connections(1) Insert the inter-unit wiring (according to local codes)into the through-the-wall PVC pipe. Ru

Pagina 106 - Pump Down

18When connecting each power wire to the correspondingterminal, follow the instructions “How to connect wiringto the terminal” and fasten the wire sec

Pagina 107 - Service Valve Connections

193-9. Mounting(1) To install the indoor unit, mount the indoor unit ontothe 3 tabs on the upper part of the rear plate.(2) Hold down the air discharg

Pagina 108 - 8. Address Switch

20Hole in wallBent partNarrow tubeWide tubeRear panelFig. 38Drain cap Drain hoseClampFig. 39 Left-side tubing(1) Lead the tubing and drain hose throu

Pagina 109

21To unmount indoor unitPress the 2 ▲ marks on the lower part of the indoor unitand unlatch the tabs. Then lift the indoor unit andunmount. (Fig. 42)3